CENTRE BREAK DISCONNECTOR COMPRISES

a. Hamper Assembly e. Inter phase Coupling Pipes
b. Support Insulator f. Support Structure
c. Disconnector Base g. Operating Mechanism
d. Inter Stack Coupling Pipes h. Interlocks
A. HAMPER ASSEMBLY

The Hamper assembly consists of two moving arms called the male and female arms, each mounted onto the top of the rotating support insulators. The arms are made out of tubular or channel sections of aluminium alloy depending on the current and voltage ratings of the disconnectors. The male copper contact and female copper contact fingers are silver plated and mounted onto the arms.

The male and female hamper assemblies are connected to the terminal stem by using multiple, flexible copper strips for the safe transfer of current from the moving arm to the fixed terminal stem of the disconnector. The copper flexible is bolted firmly at one end to the rotating arm and at the other end of the terminal stem.

The contact between the male and female contact is a line contact and the contacts provided are of the reverse loop type. Each contact finger is provided with a contact spring which, ensures that the required pressure of approximately nine kgs. per pair of fingers is maintained.

The terminal stem onto which the terminal connector is fixed is made of aluminium alloy for 420kV disconnectors upto 2500 Amps & 245kV Disconnectors of 2500 Amps; and of copper for all 245kV and below Disconnectors upto 2000A. For 3150Amps rated disconnectors, only copper terminal stems are used. Where copper terminals are provided the terminals are tin plated for connection to aluminium alloy terminal connectors. Contact corona rings are provided at the male and female hampers wherever necessary.

B. SUPPORT INSULATORS

The support insulators in the case of the centre break disconnectors are used to support metallic hampers of the disconnectors and to rotate through 90 degrees to open and close the disconnectors, to provide necessary insulation between live parts and ground. Insulator corona rings are provided on the insulators wherever necessary.

C. DISCONNECTOR BASE

Disconnector base is made out of welded assembly. The base consists of two flanges at either ends for mounting the support insulators. These flanges are provided with the necessary holes at the required pitch circle diameter to match the holes provided on the base flange of the insulator. The flanges are welded on the bearing shaft and are assembled with two numbers taper roller bearings, Ball bearings with Al casting. These taper roller bearings are seated one on the top and one on the bottom of the base assembly and these ensure free and smooth movement of disconnector arms. Bearing covers are provided to ensure that water and dust do not enter the bearings. Provision is made at the two ends of the bases to mount earth switches if required. Provision is also made on the base for mounting the mechanical constructional interlock between disconnector and earth switch wherever required.

The base is provided with mounting arrangement at two points for fixing the disconnector base with the supporting structure.

Earthing pad / earthing studs are provided at two points at the extreme ends of the base for connecting to the customers sub station earthing system.

D. INTER STACK COUPLING PIPES

Inter stack coupling pipes are provided to couple the two columns on the same phase of disconnector so as to ensure simultaneous rotation of the two poles columns driven by the common operating mechanism. The coupling pipes are linked to the base flange on which the insulator is mounted by metallic pin to ensure easy assembly / dismantling at site. Normally the inter pole coupling pipes are assembled on to the base and set at factory prior to despatch from works.

E. INTER PHASE COUPLING PIPES

Inter Phase coupling pipes are provided to couple the three phases of the Disconnector and operate all the three phases from a common operating mechanism in the case of Mechanically Ganged three pole Disconnectors. These are not required in the case of single pole Disconnectors where each pole is operated by its own operating mechanism. The coupling pipes are linked to one base flange on each phase of the three pole disconnector. These are despatched loose and are to be assembled at site. Provision is available to do minor adjustments in length of the coupling pipe to suit site conditions.

F. SUPPORT STRUCTURE

Wherever specified, support structure of tubular types for 420kV disconnector and lattice type for 245kV and below disconnectors with necessary foundation bolts can be supplied. Plates are welded on to this tubular support structure fabricated out of welded sheet steel for 420kV Disconnectors for mounting the operating mechanism boxes, the operating mechanisms of the disconnectors / earth switches are mounted on to the structure on plates provided, being bolted with the angles that are provided on the mechanism box. The height of this support structure can be varied to accommodate the bus height as required by the purchaser's layout and system.

G. OPERATING MECHANISM

Motor Operating mechanism or manual Operating Mechanisms can be supplied as per customer requirement.

H. INTERLOCKS

The following interlocks are provided for the Horizontal centre break disconnectors.

A Mechanical constructional interlock between the disconnector and earth switch has been provided to ensure that the Earth Switch can be closed only when the Disconnector is in the open position and vive versa.

An electro-mechanical castle key type interlock has been provided in each motor operating mechanism for interlocking between manual and motor operation of Disconnector / Earth switch. This ensures that the motor circuit is cut off when the manual operation is under progress.

In some cases, only electrical bolt coils are provided as interlocks solely controlled by electrical circuits.

Based on customer needs either Electro-mechanical or Electrical interlocks will be provided.

Electrical contact is provided in the Electrical circuit of the Motor Operating Mechanism for the Purchaser to write in the external interlocks if any to ensue that the Disconnectors / Earth switch can be operated only if all the interlocking conditions are satisfied.

NOTE :

Horizontal Centre Break Disconnector can be supplied by us either without Earth switch, with Single Earth switch or with Double Earth switch.

Centre Break Disconnectors are normally offered for Horizontal, normal level, upright mounting. But on request these can be offered for other types of mounting like series, vertical, higher, level, underhung, tandem etc.,

Horizontal Centre Break disconnectors / Earth switches supplied by us are generally Mechanically Ganged for operation of all three poles from a common operating mechanism cabinet. However we can supply 420kV Centre Break Disconnectors with the three poles being operated by 3 separate mechanisms, which are electrically ganged to operated together, if so desired by the purchaser.

 

>>Top